AL802ULADAJ - 3 -
Power Supply Specifications:
Stand-by Specification
s:
Note: Unit is equipped with 1 amp max. auxiliary output: AUX” will remain battery backed up during power
outag
e. For loads connected to AUX” please, refer to battery “Stand-by Specifications” above for ratings. When
loads are connected to AUX” output during alarm condition, the remaining outputs may, not exceed 8 amp total
alarm current (example:AUX = 1 amp, outputs up to 7 amp).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA
72/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
Carefully review:
Application Guide f
or AL602ULADAJ,AL802ULADAJ,AL1002ULADAJ
Power Supply Specifications (pg. 3)
Stand-by Specifications (pg. 3)
Output Programming Selection Table (pg. 4)
Sync Mode Selection Table (pg. 4)
Terminal Identification Table (pgs. 5-6)
LED Status Indication Table (pg. 6)
1. Mount the unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install tw
o upper fasteners and screws in the wall with the screw heads
protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position
of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the
enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten
all screws (Enclosure Dimensions, pg. 12).
Secure enclosure to ear
th ground (Fig. 1, pg.3).
2. Connect the line (L), ground (G), and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz)
dedicated to the F
ire Alarm System.
3. Measure output voltage before connecting devices.This helps avoid potential damage.
4. Connect battery to terminals marked [+ BAT --] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and
desired output signal type (Output Programming Selection Table, pg. 4).
6. Connect FACP output to desired AL800LGK logic board inputs, and notification appliances to desired AL800LGK
logic board outputs (see Application Guide).
L G N
line
ground
neutral
Fig. 1
AC Input:
120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit.
Output:
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current.
One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total
output current must not exceed current 8 amp in Alarm Condition.
Battery:
Use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH
batteries connected in series.
Stand-by/Alarm Current
Consumption:
90mA/175mA
EOL Resistor (end of line):
2.2K (2200 ohm), Altronix Model # AL-EOL22 (included).
Ground fault maximum
test impedance:
1000 ohm.
Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24VDC/7AH 24 Hours 8 amp/5 minutes ---
24VDC/12AH
(use two (2) 12VDC batteries in series)
24 Hours 8 amp/5 minutes 50mA
24VDC/36AH 24 Hours 8 amp/5 minutes 1 amp