Altronix AL842ULADA Installation Instructions Instrukcja Użytkownika Strona 8

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 12
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 7
- 8 - AL842ULADA
Optional hookups:
1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to
reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional
supervisorymonitoring.
ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 2a)tothe
commontroubleinput.
2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman
addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.
4- ACLocal[NC,C,NO]shouldconnecttothehostcontrolpanelforlocalannunciationof
thetroublecondition.
Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe
shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 2b).
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel
(26.2-26.4VDC recommended range).
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltage
bothatthebatteryterminalandattheboardterminalsmarked[+BAT--]toensurethatthereisnobreakinthebattery
connectionwires.
Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis
10amp@250V,Outputfuseratingis15amp@32V.
Note:Maximumchargingcurrentis3.2amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.